The followings are about the result of water analysis which is averaged during from 01-Jun-97 to 31-Jul-98.

Thailand Raw Water Quality of Each Industrial Estate...
<< Back
Bangchan
Kabinburi*
Bangpa-in*
Rayong Ind.Estate
304 Ind.Estate
Amatacity (Rayong)
Turbidity
-
1
0.6
5
4.2
8
pH
8.1
7.3
7.8
7.5
7.1
7.9
EC
817
476
1,100
123
190
105
Total Hardness (ppm as CaCO3
88
188
110
41
51
39
Calcium Hardness (ppm as CaCO3)
-
-
-
-
-
-
Total Iron (ppm as Fe++)
0.02
0.21
0.20
0.44
0.25
-
M-Alkalinity (ppm as CaCO3)
301
227
440
31
20
-
Chloride Ion (ppm as Cl-)
6
6
43
12
12
-
Sulfate Ion (ppm as SO4=)
71
10
68
3
53
-
Silica (ppm as SiO2)
27
39
47
16
8
-
Mass Balance for Cation & Anion Ion
Ca++ (ppm as CaCO3)
88
188
110
41
51
39
Mg++ (ppm as CaCO3)
-
-
-
-
-
-
Na+ (ppm as CaCO3)
296
57
461
10
42
-
Total Cation (ppm as CaCO3)
384
245
571
51
92
39
Cl- (ppm as CaCO3)
9
8
60
17
17
-
SO4= (ppm as CaCO3)
74
10
71
3
56
-
HCO3- (ppm as CaCO3)
301
227
440
31
20
-
Total Anion (ppm as CaCO3)
384
245
571
51
92
-
SiO2 (ppm as CaCO3)
22
33
39
13
7
-
Total Anion + SiO2 (ppm as CaCO3)
407
248
610
64
99
-